281
Pulse Outputs
Section 7-2
ORIGIN SEARCH:
ORG(889)
ORG(889) performs an origin search or origin return operation. The required
PLC Setup parameters must be set before performing an origin search or ori-
gin return operation.
Origin Search
Positions the system to the origin based on the origin proximity input and ori-
gin input signals.
Origin Return
Returns the system from its present position to the pre-established origin.
Operand
Contents
P
Port specifier
0000 hex: Pulse output 0
0001 hex: Pulse output 1
M
Output
mode
Bits 0 to 3
Mode
0000 hex: Relative pulse output
0001 hex: Absolute pulse output
Bits 4 to 7
Direction
0 hex: CW
1 hex: CCW
Bits 8 to 11
Pulse output method (See note.)
0 hex: CW/CCW
1 hex: Pulse + direction
Bits 12 to 15 Not used. (Always 0 hex.)
S
First
set-
tings
table
word
S
Acceleration rate:
0001 to FFFF hex (1 to 65,535 Hz)
Specify the increase or decrease in the frequency per
pulse control period (4 ms).
S+1
Deceleration rate:
0001 to FFFF hex (1 to 65,535 Hz)
Specify the increase or decrease in the frequency per
pulse control period (4 ms).
S+2 and
S+3
S+2 and S+3 contain the target frequency setting, in
units of 1 Hz. (S+2 contains the rightmost 4 digits and
S+3 contains the leftmost 4 digits.)
00000001 to 000186A0 hex (0 Hz to 100 kHz)
S+4 and
S+5
S+4 and S+5 contain the number of pulses setting. (S+4
contains the rightmost 4 digits and S+5 contains the left-
most 4 digits.)
Relative pulse output:
0000 0000 to 7FFF FFFF hex (0 to 2,147,483,647)
Absolute pulse output:
8000 0000 to 7FFF FFFF hex (-2,147,483,648 to
2,147,483,647)
F
First starting fre-
quency word
F and F+1 contain the starting frequency setting, in units
of 1 Hz. (F contains the rightmost 4 digits and F+1 con-
tains the leftmost 4 digits.)
0000 0000 to 000186A0 hex (0 Hz to 100 kHz)
ORG(889)
P
C
P:
Port specifier
C:
Control data
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......