411
Serial Communications
Section 8-3
CPU Unit Serial Gateway Function Specifications
Note
If a CJ-series Serial Communications Unit is connected via a CJ Unit Adapter,
messages can also be converted to Modbus-ASCII or Host Link FINS. Refer
to the SYSMAC CS/CJ Series Serial Communications Boards/Units Opera-
tion Manual (W336) for details.
8-3-5
Serial PLC Links
Overview
Serial PLC Links can be used to allow data to be exchanged among CP1L-
EL/EM and CJ1M CPU Units via the RS-422A/485 or RS-232C Option Boards
mounted to the CPU Units without requiring special programming. The com-
munications mode in the PLC Setup must be set to the Serial PLC Link Mode
to enable this functionality.
• Either serial port 1 or 2 can be used. (See note.)
• Words are allocated in memory in the Serial PLC Link Words (CIO 3100
to CIO 3199).
• A maximum of 10 words can be transferred by each CP1L-EL/EM CPU
Unit, but the number of linked words can be set to fewer words. (The size
must be the same for all CP1L-EL/EM CPU Units.)
Note
Serial PLC Links cannot be used on serial ports 1 and 2 at the same time. If
one port is set as a Serial PLC Link slave or master, it will not be possible to
set the other port for a Serial PLC Link. A PLC Setup error will occur if an
attempt is made to set both ports for Serial PLC Links.
Item
Specification
Pre-conversion data
FINS (via FINS network, Host Link FINS, toolbus, NT Link,
or CPU bus)
Conversion functions
FINS commands addressed to serial port 1 or 2 on the CPU
Unit are converted to CompoWay/F commands (after
removing the header) if the FINS command code is 2803
hex and to Modbus-RTU commands (after removing the
header) if the FINS command code is 2804 hex.
Post-conversion data
CompoWay/F command or Modbus-RTU command
Serial communications
method
1:N half-duplex
Maximum number of
nodes
31
Enabling serial commu-
nications mode
Serial Gateway Mode
Response timeout
The time from when a message converted to a different pro-
tocol is set until a response is received is monitored by the
serial gateway function.
Default: 5 s, User setting: 0.1 to 25.5 s
Note
A FINS response code of 0205 hex (response time-
out) is sent to the source of the FINS command if a
timeout occurs.
Send delay function
None
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......