468
Analog Input Units
Section 9-2
■
Set Data
• The Analog Input Unit will not start converting analog input values until
the set data has been written.
• Once the range code has been set, it is not possible to be changed while
power is being supplied to the CPU Unit. To change the range code, turn
the CPU Unit OFF then ON again.
Averaging
Set whether averaging is to be used for set data. When the averaging bit is
set to 1, the average (moving average) for the past eight inputs is output as
conversion data.
Reading Analog Input
Conversion Values
Read the conversion value storage area with the ladder program. With word
m as the last input word allocated to the CPU Unit or an already-connected
Expansion Unit, the A/D conversion data will be output to the following words
m+1 to m+4.
Startup Operation
After the power is turned ON, it will require two cycle times plus approximately
50 ms before the first conversion data is stored in the input words. Therefore,
create a program as shown below, so that the ladder can start to operate with
valid conversion data in input words.
The analog input data will be 0000 until the first conversion data is stored in
the input words.
15 0
1 0 0 0 0 0 0
8 7 6 5 4 3 2 1
15 0
1 0 0 0 0 0 0
8 7 6 5 4 3 2 1
0
0
Even if analog inputs are not
used, bits 15 in words n+1
and n+2 must be set to 1.
Even if analog inputs are not
used, bits 15 in words n+1
and n+2 must be set to 1.
Wd (n+1)
Wd (n+2)
Analog input 1
Analog input 2
Analog input 3
Analog input 4
Averaging
0
No
1
Yes
Input Use
0
No
1
Yes
Range code
Analog input range
−
10 to 10 V
0 to 10 V
1 to 5 V or 4 to 20 mA
0 to 5 V or 0 to 20 mA
00
01
10
11
MOV(021)
2
D0
0005
TIM
#0002
T0005
Always ON Flag
P_On
TIM0005 is started when the power is
turned ON. After 0.2 s (200 ms) elapses,
the TIM0005 contact turns ON and the
analog input 1 conversion data stored in
word 2 is transferred to D0.
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......