9 - 15
MELSEC-A
9 MAIN POSITIONING CONTROL
9.1.4 Confirming the current value
Values showing the current value
The following two types of addresses are used as values to show the position in
the AD75.
These addresses ("current feed value" and "machine feed value") are stored in the
monitor data area, and used in monitoring the current value display, etc.
Current feed value
•
This is the value stored in "
Md.29 Current feed value".
•
This value has an address established with a "machine zero point
return" as a reference, but the address can be changed by changing
the current value to a new value.
•
This value is updated every 56. 8ms.
Machine feed value
•
This is the value stored in "
Md.30 Machine feed value".
•
This value always has an address established with a "machine zero
point return" as a reference. The address cannot be changed, even if
the current value is changed to a new value.
•
This value is updated every 56. 8ms.
The "current feed value" and "machine feed value" are used in monitoring the
current value display, etc.
0
1 to
Md. 29 Current feed value
t
V
Zero point
20000
Current value changed to
20000 with the new current
value command
0
1 to
Md. 30 Machine feed value
Address after the current
value is changed is stored
10000
10000
Address does not change even
after the current value is changed
Fig. 9.8 Current feed value and machine feed value
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...