5 - 2
MELSEC-A
5 DATA USED FOR POSITIONING CONTROL
5.1 Types of data
5.1.1 Parameters and data required for control
The parameters and data required to carry out control with the AD75 include the
"setting data", "monitor data" and "control data" shown below.
Setting data
(Data set beforehand according to the machine and application, and stored in the flash ROM.)
Parameters
Positioning
parameters
Basic parameters 1
Set according to the machine and applicable
motor when system is started up.
Note)
If the setting of the basic parameters 1 is incorrect, the rotation direction
may be reversed, or no operation may take place.
Basic parameters 2
Detailed parameters 1
Detailed parameters 2
Set according to the system configuration when
the system is started up.
Note)
Detailed parameters 2 are data items for using the AD75 functions to the fullest.
Set as required.
Zero point
return
parameters
Zero point return basic parameters
Zero point return detailed parameters
Set the values required for carrying
out zero point return control.
Positioning data
Positioning data
Set the data for "main positioning control".
Positioning start
information
Start block data
Set the start block data for "advanced positioning control".
Condition data
Set the condition data for "advanced positioning control".
Memo data
Set the condition judgment values for the condition
data used in "advanced positioning control".
Indirectly specification data
Set when indirectly specificating the positioning
data No. .
to
)
Pr.1
)
Pr.58
to
)
Pr.1
)
Pr.44
to
)
Pr.45
)
Pr.58
to
)
Da.1
)
Da.9
to
)
Da.10
)
Da.18
to
)
Da.14
)
Da.18
to
)
Da.10
)
Da.13
The data is set with the sequence program or peripheral device.
In this chapter, the method using the peripheral device will be explained.
(Refer to "Point" on the next page.)
The basic parameters 1, deteailed parameters 1, and zero point return parameters become valid
when the PLC READY signal [Y1D] turns from OFF to ON.
The basic parameters 2 and detailed parameters 2 become valid immediately when they are
written to the buffer memory, regardless of the state of the PLC READY signal [Y1D].
Even when the PLC READY signal [Y1D] is ON, the values or contents of the following can
be changed: basic parameters 2, detailed parameters 2, positioning data, and positioning
start information.
◊
◊
◊
◊
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...