12 - 61
MELSEC-A
12 CONTROL AUXILIARY FUNCTIONS
(4) Setting the M code output function
The following shows the settings to use the "M code output function".
(a) Set the M code No. in the positioning data "
Da.9 M code".
(b) Set the timing to output the M code ON signal (XD, XE, XF).
Set the required value in the following parameter, and write it to the AD75.
The set details are validated at the rising edge (OFF ON) of the PLC READY
signal (Y1D).
Buffer memory address
Setting item
Setting
value
Setting details
Axis 1 Axis 2 Axis 3
Pr.19
M code ON signal
output timing
Set the timing to output the M code ON signal.
0: WITH mode
1: AFTER mode
25 175 325
* Refer to section "5.2 List of parameters" for setting details.
(5) Reading M codes
"M codes" are stored in the following buffer memory when the M code ON signal
turns ON.
Buffer memory address
Monitor item
Monitor
value
Storage details
Axis 1 Axis 2 Axis 3
Md.32
Valid M code
The M code No. (
Da.9 M code) set in the
positioning data is stored.
806 906 1006
* Refer to section "5.6 List of monitor data" for information on the storage details.
The following shows a sequence program example for reading the " Md.32 Valid
M code" to the PLC CPU data register (D110). (The read value is used to
command the auxiliary work.)
Read M codes not as "rising edge commands", but as "ON execution
commands".
M code ON signal
K1
D110
K806
H0
FROM
ON execution command
D110: valid M codes
Example
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...