12 CONTROL AUXILIARY FUNCTIONS
(3) Setting the command in-position function
To use the "command in-position function", set the required value in the
parameter shown in the following table, and write it to the AD75.
The set details are validated at the rising edge (OFF ON) of the PLC READY
signal (Y1D).
Setting item
Setting
value
Setting details
Factory-set
initial value
Pr.17
Command in-
position width
Turn ON the command in-position flag, and set the
remaining distance to the stop position of the position
control.
100
* Refer to secion "5.2 List of parameters" for setting details.
(4) Confirming the command in-position flag
The "command in-position flag" is stored in the following buffer memory.
Buffer memory address
Monitor item
Monitor
value
Storage details
Axis 1 Axis 2 Axis 3
Md.40
Status
The command in-position flag is stored in the
"b2" position.
817 917 1017
* Refer to section "5.6 List of monitor data" for information on the storage details.
REMARK
•
Parameters are set for each axis.
•
It is recommended that the parameters be set whenever possible with the AD75
software package. Execution by sequence program uses many sequence
programs and devices. The execution becomes complicated, and the scan times
will increase.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...