4 - 11
MELSEC-A
4 INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT
4) Cable clamp fitting position and shielded cable grounding
method
AD75
20 to 30cm
AD75CK
Inside control panel
[How to ground shilded cable using AD75CK]
Shielded cable
Shielding wires
Screw for mounting to control cabinet (M4 screw)
Grounding terminal
Grounding terminal installation screw (M4x8 screw)
AD75CK can ground up to four shielded cables having about 7 mm or smaller outside
diameters. (For details, refer to AD75CK cable clamp operation manual <IB-68682>.)