5 - 121
MELSEC-A
5 DATA USED FOR POSITIONING CONTROL
Storage buffer
memory address
Setting value
Default value
Axis 1 Axis 2 Axis 3
Set with a decimal.
K
Step mode
Setting value
0: Carry out step operation with deceleration unit
1: Carry out step operation with data No. unit
0 1173
1223
1273
Set with a decimal.
K
Step start information
Setting value
After the step start request is accepted,
"0" is stored by the OS.
1: Step continue
2: Restart
0 1174
1224
1274
Set with a decimal.
K
1
Skip command
Setting value
After the skip request is accepted, "0" is stored by the OS.
1: Decelerate to a stop, and then carry
out the next positioning. (Skip request)
(Set by sequence program)
0 1175
1225
1275
Set with a decimal.
New torque value
Setting value
K
1 to Torque limit
setting value
Pr.18
0 1176
1226
1276
Set with a decimal.
K
Positioning starting
point No.
1 to 50
Setting value
When continuous operation is interrupted, "0" is stored automatically.
0 1178
1228
1278
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...