10 - 19
MELSEC-A
10 ADVANCED POSITIONING CONTROL
10.4.2 Condition data setting examples
The following shows setting examples for "condition data".
(1) Setting the device ON/OFF as a condition
[Condition] Device "X0" (=AD75 READY) is ON
Da.14
Condition target
Da.15
Condition
operator
Da.16
Address
Da.17
Parameter 1
Da.18
Parameter 2
01
H
: Device X
07
H
:
DEV=ON
– 0 –
(2) Setting the numeric value stored in the "buffer memory" as a
condition
[Condition]
The value stored in buffer memory addresses "800, 801" (="
Md.29 Current
feed value") is "1000" or larger.
Da.14
Condition target
Da.15
Condition
operator
Da.16
Address
Da.17
Parameter 1
Da.18
Parameter 2
04
H
: Buffer memory
(2 words)
03
H
:
≤
P1
800 1000 –
(3) Designating the axis and positioning data No. to be simultaneously
started in "simultaneous start"
[Condition]
Simultaneously starting "axis 2 positioning data No.3".
Da.14
Condition target
Da.15
Condition
operator
Da.16
Address
Da.17
Parameter 1
Da.18
Parameter 2
05
H
: Positioning
data No.
0A
H
: Axis 2
designation
–
High-order 16
bits "0003
H
"
–
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...