14 - 8
MELSEC-A
14 TROUBLESHOOTING
Division of
error
Error
code
Error name
Description
Action at occurrence of error
103
Test mode fault
during operation
Communication between the personal
computer and AD75 is interrupted in test mode.
Stopping according to sudden stop (stopping
group 3) setting (deceleration and stop/sudden
stop) selected in detail parameter 2 (However,
deceleration and stop only during manual pulse
generator operation)
104
Hardware stroke
limit (+)
An upper hardware stroke limit signal (FLS) is
turned OFF.
105
Hardware stroke
limit (-)
A lower hardware stroke limit signal (RLS) is
turned OFF.
Stopping according to sudden stop (stopping
group 1) setting (deceleration and stop/sudden
stop) selected in detail parameter 2 (However,
deceleration and stop only during manual pulse
generator operation)
106
Stop signal ON
at start
A start request is issued while the stop signal is
turned ON.
Positioning start is not carried out.
Common
107
PLC READY
OFF --> ON in
busy
The “PLC READY” signal is turned OFF while
the busy signal is turned ON.
The AD75 READY signal (X0) is not turned
OFF.
Zero point
return
201
Start at zero
point
Near-point dog method machine zero point
return is started with an invalidated zero point
return retry setting when the zero point return
completion flag is ON.
Machine zero point return start is not carried
out.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...