4 - 12
MELSEC-A
4 INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT
(Poor examples and improved examples are shown below.)
Short wiring with the AD75 and
drive unit placed in proximity,
and the connection cable and
other cables separated
(without passing through duct).
Control
panel
Relay
Drive
unit
Drive
unit
Inverter
Wiring duct
Changed
Relay
Relay
PLC
AD
75
Relay
Inverter
Relay
Relay
PLC
AD
75
Control
panel
Drive
unit
Drive
unit
Wiring duct
(12) The influence of noise may be reduced by installing ferrite cores to the cable
connected to the AD75 as a noise reduction technique.
For the noise reduction techniques related to connection with the servo amplifier,
also refer to the instruction manual of the servo amplifier.
(13) If compliance with the EMC directive is not required, the influence of external
noise may be reduced by making the configuration compliant with the EMC
directive.
For the configuration compliant with the EMC directive, refer to Chapter 3 "EMC
directive and low voltage directive" in the User's Manual (Hardware) of the used
CPU module.
(14) Installing ferrite cores and noise filter to the power supply line of the PLC as
noise reduction techniques may have effects on external noise.
(Example)
• Ferrite cores
Type: ZCAT3035-1330 (TDK ferrite core)
• Noise filter
Type: MXB-1210-33 (DENSEI-LAMBDA noise filter)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...