12 - 23
MELSEC-A
12 CONTROL AUXILIARY FUNCTIONS
(2) Precautions during control
During interpolation control, speed limiting is carried out at the reference axis
side setting value.
(The speed limit will not function on the interpolation side.)
(3) Setting the speed limit function
To use the "speed limit function", set the "speed limit value" in the parameters
shown in the following table, and write them to the AD75.
The set details are validated after they are written to the AD75.
Setting item
Setting
value
Setting details
Factory-set
initial value
Pr.7 Speed limit value
Set the speed limit value (max. speed during control).
0
Pr.32
JOG speed limit
value
Set the speed limit value during JOG operation (max.
speed during control). (Note that "
Pr.32 JOG speed
limit value" shall be less than or equal to "
Pr.7
Speed limit value".)
0
* Refer to section "5.2 List of parameters" for setting details.
REMARK
•
Parameters are set for each axis.
•
It is recommended that the parameters be set whenever possible with the AD75
software package. Execution by sequence program uses many sequence
programs and devices. The execution becomes complicated, and the scan times
will increase.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...