5 - 81
MELSEC-A
5 DATA USED FOR POSITIONING CONTROL
Da.17 Parameter 1
Set the parameters as required for the " Da.15 Condition operator".
Da.15 Condition operator
Setting value
Setting details
01
H
:
∗∗
=P1
06
H
:
∗∗≤
P1, P2
≤∗∗
Value
Set the "P1" value.
07
H
: DEV=ON
08
H
: DEV=OFF
Value
(Bit No.)
Set the device's bit No.
X : 0
H
to F
H
, Y : 10
H
to 1D
H
09
H
: Axis 1 designation
0E
H
: Axis 2 and axis 3 designation
Value
(Positioning data No.)
Set the positioning data No. for starting axis 1 and axis 2.
Low-order 16-bit:
Axis 1 positioning data No. 1 to 600 (01
H
to 258
H
)
High-order 16-bit:
Axis 2 positioning data No. 1 to 600 (01
H
to 258
H
)
Da.18 Parameter 2
Set the parameters as required for the " Da.15 Condition operator".
Da.15 Condition operator
Setting value
Setting details
01
H
:
∗∗
=P1
04
H
:
∗∗≥
P1
–
Not used. (There is no need to set.)
05
H
: P1
≤∗∗≤
P2
Value
Set the "P2" value.
06
H
:
∗∗≤
P1, P2
≤∗∗
07
H
: DEV=ON
08
H
: DEV=OFF
09
H
: Axis 1 designation
0A
H
: Axis 2 designation
0B
H
: Axis 1 and axis 2 designation
–
Not used. (There is no need to set.)
0C
H
: Axis 3 designation
0D
H
: Axis 1 and axis 3 designation
0E
H
: Axis 2 and axis 3 designation
Value
(Positioning data No.)
Set the positioning data No. for starting axis 3.
Low-order 16-bit:
Axis 3 positioning data No. 1 to 600 (01
H
to 258
H
)
High-order 16-bit: No setting
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...