5 - 119
MELSEC-A
5 DATA USED FOR POSITIONING CONTROL
Storage buffer
memory address
Setting value
Default value
Axis 1 Axis 2 Axis 3
Set with a decimal.
K
Manual pulse generator enable flag
Setting value
0: Disable manual pulse generator operation
1: Enable manual pulse generator operation
0 1167
1217
1267
Set with a decimal.
K
Manual pulse generator
1 pulse input magnification
1 to 100
Setting value
1
1168
1169
1218
1219
1268
1269
Set with a decimal.
K
Zero point return request flag OFF request
Setting value
After the zero point return request turns OFF, "0" is stored by the OS.
(Indicates that the zero point return request flag OFF request is completed.)
1: Turn OFF the "zero point return request
flag" that is ON.
(Set by sequence program)
1
0 1170
1220
1270
Set with a decimal.
K
External start valid
Setting value
0: Invalidate external start
1: Validate external start
0 1171
1221
1271
Set with a decimal.
K
Step valid flag
Setting value
0: Do not carry out step operation
1: Carry out step operation
0 1172
1222
1272
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...