12 - 84
MELSEC-A
12 CONTROL AUXILIARY FUNCTIONS
(3) Control details and setting
The following shows the control details and setting when the indirectly
specification data set to the indirectly specification No. 8001 of axis 1 is started.
1150
Y10
4500
PLC CPU
8001
1
1
2
4
ON
3
AD75
Input/output signal
Drive unit
Buffer memory
Controlled with
the specified
positioning data
: When making a positioning start at
the scan next to positioning completion,
provide X1 as an interlock to make
a start after Y10 is turned OFF and
X1 then turns OFF.
1) Set "8001" to "
Cd.11
Positioning start No.".
2) Set the positioning data No. to the "indirectly specification data" to be started. (In this case, set "1".)
3) Turn ON the start signal.
4) The positioning data set to the "positioning data No. for indirectly specification No. 8001" is started.
Fig. 12.42 Indirectly specification function operating procedure (for axis 1)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for A1SD75P1-S3
Page 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...