15. MR-J3W-0303BN6 SERVO AMPLIFIER
15 - 44
15.6 Troubleshooting
POINT
This section explains troubleshooting only for MR-J3W-0303BN6. For the
troubleshooting other than MR-J3W-0303BN6, refer to chapter 8.
Alarm No.: 10
Name: Undervoltage
Stop system: All axes
Alarm content
The voltage of the control circuit power supply has dropped.
The voltage of the main circuit power supply has dropped.
Display
Detail name
Cause
Check method
Check result
Action
The connector was
disconnected or
connected loosely.
Connect it correctly.
1) The control circuit power
supply connector was
disconnected. Loose
connection
Check the control circuit
power supply connector.
It has no problem.
Check 2).
It is lower than
17VDC.
Increase the voltage of the
control circuit power
supply.
2) The voltage of the control
circuit power supply is low.
Check if the voltage of
the control circuit power
supply is lower than
17VDC.
The voltage is over
17VDC.
Check 3).
10.1 Voltage drop in
the control
circuit power
3) An instantaneous power
failure has occurred for
longer than 15ms.
Check if the power has
a problem.
It has a problem.
Review the power.
It is disconnected.
Connect it correctly.
1) The main circuit power
supply connector was
disconnected.
Check the main circuit
power supply connector. It has no problem.
Check 2).
The voltage of the
main circuit power
supply is 35VDC or
lower when 48VDC
is set for the main
circuit power supply,
or 15VDC or lower
when 24VDC is set
for the main circuit
power supply.
Increase the voltage of the
main circuit power supply.
2) The voltage of the main
circuit power supply is low.
Check if the voltage of
the main circuit power
supply is 35VDC or
lower when 48VDC is
set for the main circuit
power supply, or 15VDC
or lower when 24VDC is
set for the main circuit
power supply.
It is over 35VDC
when 48VDC is set
or over 15VDC when
24VDC is set.
Check 3) and 4).
10.2 Voltage drop in
the main circuit
power
3) The alarm has occurred
during acceleration.
The bus voltage is
35VDC or higher when
48VDC is set for the
main circuit power
supply, or 15VDC or
higher when 24VDC is
set for the main circuit
power supply.
The voltage is
35VDC or lower
when 48VDC is set
for the main circuit
power supply, or
15VDC or lower
when 24VDC is set
for the main circuit
power supply.
Increase the acceleration
time constant. Or increase
the power supply capacity.
Summary of Contents for MELSERVO-J3W Series
Page 17: ...8 MEMO ...
Page 27: ...1 FUNCTIONS AND CONFIGURATION 1 10 MEMO ...
Page 87: ...4 STARTUP 4 14 MEMO ...
Page 117: ...5 PARAMETERS 5 30 MEMO ...
Page 129: ...6 GENERAL GAIN ADJUSTMENT 6 12 MEMO ...
Page 185: ...10 CHARACTERISTICS 10 8 MEMO ...
Page 241: ...11 OPTIONS AND AUXILIARY EQUIPMENT 11 56 MEMO ...
Page 274: ...13 USING A LINEAR SERVO MOTOR 13 25 1 2 3 4 ...