2.5 Causes and countermeasures for ELECYLINDER alarms
C2-34
ME0384-4A
C
ha
pt
er
2
Troubl
es
hoot
ing
M
ai
nt
ena
nc
e
Sec
tion
[Alarm group E: Supply voltage/power capacity abnormality alarm]
An abnormality occurred in the power supply voltage and capacity supplied to the rear of the
ELECYLINDER.
No.
Cause
Countermeasure
1
The ELECYLINDER may be being used under
conditions exceeding the specifications
described in the catalog.
Check the specification values such as payload,
acceleration/deceleration and speed, and adjust
them appropriately.
2
The power supply voltage has been detected
outside the range of 21.6V to 26.4V.
Inspect with a tester to see whether the power
supply voltage is in the range of 21.6 V to 26.4 V.
If it is out of range, the 24VDC power supply
voltage has insufficient capacity.
Refer to our catalog for the required capacity and
improve the power supply environment.
3
If this alarm recurs after performing the
inspection above and improving the power
supply environment, it is highly likely that the
ELECYLINDER control unit has failed.
Replace the controller cover assembly of the
ELECYLINDER.
→
For the replacement method, refer to the
instruction manual for each ELECYLINDER.
Summary of Contents for Rcon
Page 12: ...ME0384 4A ...
Page 32: ...Actuator Coordinate System Intro 20 ME0384 4A ...
Page 42: ...1 3 General Specifications A1 9 ME0384 4A Specifications Section Chapter 1 RCON Overview ...
Page 45: ...ME0384 4A ...
Page 291: ...ME0384 4A ...
Page 323: ...ME0384 4A ...
Page 384: ...1 3 Startup Procedure B1 9 ME0384 4A Startup Section Chapter 1 Overview ...
Page 420: ...3 6 Precautions B3 15 ME0384 4A Startup Section Chapter 3 Absolute Reset ...
Page 588: ...6 2 Various Functions B6 81 ME0384 4A Startup Section ...
Page 837: ......
Page 838: ......