1.1 Periodic Inspection
C1-2
ME0384-4A
C
ha
pt
er
1
M
aint
enan
ce
an
d
Ins
pe
ction
M
ai
nt
ena
nc
e
Sec
tion
Periodic inspection items
The RCON systems contain electronic components that may degrade due to the operating
environment and require periodic inspection.
It is standard to conduct periodic inspection once every 6 months to one year, but the interval
should be shortened in accordance with operating environment.
No. Inspection
items
Inspection details
Judgment
criteria
Countermeasures
1
Power
supply
Measure between the
power supply terminal
block to check that the
voltage fluctuation is
within the reference range
Within voltage
fluctuation range
24 V
±
10%
Adjust so that the power supply
voltage falls within the judgment
criteria.
2 Operating
environment
Ambient temperature
(If used in a panel, the
panel temperature is
the ambient
temperature)
0 to 55°C
Measure the operating temperature
with a thermometer and adjust the
environment so that it falls within the
ambient operating temperature.
However, simple absolute units and
SCON controllers are 0 to 40°C.
Operating humidity
(Panel humidity if using
in a panel)
95% RH or less,
non-condensing
Measure the operating humidity with a
hygrometer and adjust the
environment so that it falls within the
ambient operating humidity.
Atmosphere
No corrosive or
flammable gas
Check with an odor or gas sensor.
No splatters of
water, oil, or
chemicals
Remove and shield.
No accumulated
dust, debris, salt,
or metal powder
Remove and shield.
Directly exposed to
sunlight?
Out of direct
sunlight
Shield.
Subjected to direct
vibrations or impacts?
Vibration damping
and shock-resistant
specifications should
be within the range
Install a cushion, etc., for vibration
damping and shock resistance.
Close to a noise
source?
None
Move the noise source further away or
take shielding countermeasures.
3 Mounting
status
Mounting state on each
DIN rail
No slack in unit
mounting
Re-attach and lock.
4 Connection
status Units firmly connected?
The connector
should be
tightened firmly
Tighten so that it is no longer loose.
Cable between simple
absolute unit and driver
unit securely inserted?
Insert completely Insert again.
Summary of Contents for Rcon
Page 12: ...ME0384 4A ...
Page 32: ...Actuator Coordinate System Intro 20 ME0384 4A ...
Page 42: ...1 3 General Specifications A1 9 ME0384 4A Specifications Section Chapter 1 RCON Overview ...
Page 45: ...ME0384 4A ...
Page 291: ...ME0384 4A ...
Page 323: ...ME0384 4A ...
Page 384: ...1 3 Startup Procedure B1 9 ME0384 4A Startup Section Chapter 1 Overview ...
Page 420: ...3 6 Precautions B3 15 ME0384 4A Startup Section Chapter 3 Absolute Reset ...
Page 588: ...6 2 Various Functions B6 81 ME0384 4A Startup Section ...
Page 837: ......
Page 838: ......