3.5 Field Network General Specifications
A3-19
ME0384-4A
Spec
ifi
cat
ion
s
Sec
tion
Chapt
er 3 G
at
eway
Uni
t
3.5 Field Network General Specifications
CC-Link
Cable connector name: MSTB2.5/5-STF-5.08 AU (Phoenix Contact)
Pin No.
Signal name
Description
1
DA
Signal line A
2
DB
Signal line B
3
DG
Digital ground
4
SLD
Connects the shield of shielded cables
(This connector's 5-pin FG and the control power
connector's 1 pin FG are connected internally)
5
FG
Frame ground
(This connector's 4-pin SLD and the control power
connector's 1 pin FG are connected internally)
LED display
Name
Panel
notation
Display
color
Status
Description
STATUS 0
RUN
Green
Light ON
After joining the network, refresh &
poll normal reception or refresh normal
reception
Light OFF
1. Network not joined
2. Channel carrier detected
3. Timeout
4. Hardware reset in progress
STATUS 1
ERR
Orange
Light ON
1. CRC error
2. Station number setting error when
reset canceled
(0 or 65 stations or more, including
occupied stations)
3. Baud rate setting error when reset
canceled
Blinking
(0.4 s blinking)
Value of station number or baud rate
setting changed when reset canceled
Light OFF
1. Normal communication
2. Hardware reset in progress
5
4
3
2
1
Summary of Contents for Rcon
Page 12: ...ME0384 4A ...
Page 32: ...Actuator Coordinate System Intro 20 ME0384 4A ...
Page 42: ...1 3 General Specifications A1 9 ME0384 4A Specifications Section Chapter 1 RCON Overview ...
Page 45: ...ME0384 4A ...
Page 291: ...ME0384 4A ...
Page 323: ...ME0384 4A ...
Page 384: ...1 3 Startup Procedure B1 9 ME0384 4A Startup Section Chapter 1 Overview ...
Page 420: ...3 6 Precautions B3 15 ME0384 4A Startup Section Chapter 3 Absolute Reset ...
Page 588: ...6 2 Various Functions B6 81 ME0384 4A Startup Section ...
Page 837: ......
Page 838: ......