4.2 Master Side Setting
B4-41
ME0384-4A
St
ar
tu
p
Se
ct
io
n
C
ha
pt
er
4
N
et
w
or
k
C
onf
igu
rat
ion
Look at the LED status on the front of the CC-Link master and judge whether it is
communicating normally.
No.
LED name
Applications
1
The operation status will be displayed.
Light ON
Normal operation
Light OFF
Hardware error or watchdog timer error generated
2
The status of the data link will be displayed.
Light ON
Data link in process
Light OFF
Data link not executed
3
The data transmission status will be displayed.
Light ON
Transmitting data
Light OFF
Data not transmitted
4
The data receipt status will be displayed.
Light ON
Receiving data
Light OFF
Data not transmitted
5
The error status of the master/local unit will be displayed.
Refer to Mitsubishi Electric Co., Ltd. Instruction Manual for error details.
Light ON
One of the following errors has occurred.
· Error was detected in all stations.
· The setting of "station number setting switch" or "transmission speed /
mode setting switch" of the master/local main unit is out of the range.
· The master stations are duplicated on the same network.
· There is an error in the network setting.
· CC-Link cable is disconnected. Or there is influence of noise, etc.
Light OFF
Normal operation.
6
The status of the data link error will be displayed
Light ON
Data link error has occurred in the local station.
Flashing at
regular
intervals
The setting of the master unit full-surface panel switch on the
right has been changed while the power was turned on.
Flashing at
regular
intervals
Communication is unstable due to the following causes.
· Terminal resistor is not connected. Impacted by noise
Light OFF
Normal operation.
indicates blinking.
indicate whether or not the master station and standby
master station are in operation as master stations.
CC-Link master unit
↑
Normal communication status
2
Summary of Contents for Rcon
Page 12: ...ME0384 4A ...
Page 32: ...Actuator Coordinate System Intro 20 ME0384 4A ...
Page 42: ...1 3 General Specifications A1 9 ME0384 4A Specifications Section Chapter 1 RCON Overview ...
Page 45: ...ME0384 4A ...
Page 291: ...ME0384 4A ...
Page 323: ...ME0384 4A ...
Page 384: ...1 3 Startup Procedure B1 9 ME0384 4A Startup Section Chapter 1 Overview ...
Page 420: ...3 6 Precautions B3 15 ME0384 4A Startup Section Chapter 3 Absolute Reset ...
Page 588: ...6 2 Various Functions B6 81 ME0384 4A Startup Section ...
Page 837: ......
Page 838: ......