3.8 I/O Signals
A3-115
ME0384-4A
Spec
ifi
cat
ion
s
Sec
tion
Chapt
er 3 G
at
eway
Uni
t
[2] Alarm clear input (RES) PLC output signal
●
When the [RES] signal is turned ON, the currently triggered alarm will be cleared.
●
Alarm clear may not be possible depending on the alarm itself.
Refer to "Maintenance Section Chapter 2, 2.5 Troubleshooting for ELECYLINDER alarm
groups (Page C2-30)" for detail.
[3] Position detection output backward end/forward end (LS0/LS1) PLC input signal
●
The LS signals perform the same operation as an air cylinder automatic switch.
They are not positioning complete signals.
●
The LS signals turn ON when the current ELECYLINDER position is within the detection
range configured at the backward and forward ends.
●
They turn ON when within the detection range regardless of whether the servo is ON or
OFF.
The backward end and forward end
set values' relationship to [LS0]
and [LS1] signals ON is as follows.
In this example, the LS signal
detection range is ±0.10mm.
To adjust the LS signal detection range,
open the [Edit parameters window].
Parameter No.2
[Auto switch LS signal detection range
adjustment] can be used to
make adjustments.
Backward end
0.00mm
Forward end
200.00mm
[LS0 detection range]
-0.10 to 0.10mm
[LS1 detection range]
199.90 to 200.10mm
Summary of Contents for Rcon
Page 12: ...ME0384 4A ...
Page 32: ...Actuator Coordinate System Intro 20 ME0384 4A ...
Page 42: ...1 3 General Specifications A1 9 ME0384 4A Specifications Section Chapter 1 RCON Overview ...
Page 45: ...ME0384 4A ...
Page 291: ...ME0384 4A ...
Page 323: ...ME0384 4A ...
Page 384: ...1 3 Startup Procedure B1 9 ME0384 4A Startup Section Chapter 1 Overview ...
Page 420: ...3 6 Precautions B3 15 ME0384 4A Startup Section Chapter 3 Absolute Reset ...
Page 588: ...6 2 Various Functions B6 81 ME0384 4A Startup Section ...
Page 837: ......
Page 838: ......