Troubleshooting
SiBE811001EB
211
CONVENI-PACK
8.4.32 Error Related to High Pressure Switch
Error Code
H3
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Detect continuity in the high pressure switch in the protective device circuit.
Error Decision
Conditions
While the compressor stops running, there is no continuity in the high pressure switch.
(When the condition above is met for 2 minutes continuously and the operation switch is ON.)
Supposed
Causes
Defective high pressure switch
Broken wire in the harness of high pressure switch
Defective connection of the connector of high pressure switch
Defective compressor
Defective outdoor unit PCB
Broken wire in lead wire
Troubleshooting
Replace the lead wire.
NO
Replace the high pressure
switch having no continuity in it.
∗
Normal resistance:
Not more than 10
Ω
NO
Properly connect it.
NO
Replace the outdoor unit PCB.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
YES
Is the high pressure
switch connector
properly connected
to the outdoor unit
PCB?
Stop the compressor for a period of 10
minutes, and then carry out the
following checks.
Is there continuity
in the high
pressure switch?
Is there continuity in
the lead wire?