Outline of Functions (Outdoor unit)
SiBE811001EB
103
CONVENI-PACK
(2) Capacity control
Tst_BU: Target evaporative temperature
Tsd_BU: Evaporative temperature set by DIP switch
Tsp1_BU: Temperature correction setting 1 by the BS button
Tsp2_BU: Temperature correction setting 2 by the BS button
Refer to the “Field setting” for details.
Tst_BU = T Tsp2_BU
Tsd_BU: Evaporative temperature set by DIP
switch
Lpmt_BU: Pressure conversion of target
evaporating temperature
A3P side
Tsd_BU (Lpmd_BU)
(Factory setting)
-35°C
(0.118MPa)
-45°C
(0.029MPa)
-40°C
(0.069MPa)
-30°C
(0.167MPa)