Troubleshooting
SiBE811001EB
229
CONVENI-PACK
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
While in monitor mode, check whether
the system is right-hand (control PCB
1) or left-hand (control PCB 3).
YES
While in monitor mode, check the
outdoor unit concerned.
NO
Multi system
Individual system
Go on to the next page.
(Starting failure due to aged
operation.)
Check if it is the
first time to start
after installation.
Is the individual
system applied to the
outdoor unit?
Correct the wiring then supply
the power to restart.
NO
NO
YES
Charge a right amount of
refrigerant.
Check if a right
amount of refrigerant
is charged.
NO
YES
Cancel the melting state of
refrigerant.
Check if the insulation
resistance of the compressor
is more than 100k
Ω
.
NO
YES
Fix the compressor lead wire.
Check if the
compressor lead wires
are disconnected.
YES
Open the stop valve.
Check if the stop
valve is open.
NO
YES
Cancel the melting state of
refrigerant.
Refrigerant is melting.
(The unit is out of
power supply for more
than 6 hours.)
YES
NO