SiBE811001EB
Troubleshooting
CONVENI-PACK
188
Troubleshooting
Note:
∗
1. One of the possible factors may be chattering due to rough MgS contact.
∗
2. Abnormal case
The current sensor value is 0 during STD compressor operation.
The current sensor value is more than 15.0A during STD compressor stop.
YES
NO
YES
YES
YES
Open the stop valve.
NO
Remove the obstacle.
YES
Correct the power supply
voltage.
NO
Replace the magnetic switch.
NO
Correct wiring.
NO
Replace the corresponding
current sensor (A7P or A8P).
NO
Replace the compressor.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Is the stop valve open?
Obstacle exists
around the air outlet.
Is the power supply
voltage normal?
Is the magnetic
switch (K2M, K3M, K4M)
normal? (
∗
1)
Is above wiring correct?
Check the wiring from power supply ~ current sensor (A7P, A8P) ~
MgS (K2M, K3M, K4M) ~ compressor
Is current sensor
correct? (
∗
1)