Field Setting
SiBE811001EB
133
CONVENI-PACK
7.2
Remote Input
Remote input setting procedure
Input for ON/OFF of the outdoor unit is performed remotely using the onsite switch.
Wiring onsite from the terminal strip X3M (1 and 2).
Operation: Normal cooling operation. (Stops at the low pressure cut value.)
Stop (OFF): Forced thermo. OFF.
When installing a remote switch in the booster unit, wiring to the terminal
strip X2M (1 and 2) of the electric component of the booster unit.
<Input signal>
Normal 'a' contact
The input current per contact is approximately 12mA. For input contacts, use those for minute electric current.
Use a minimal application load (usable under DC12V and under 1mA).
∗
When using switches other than for minute electric currents, use contact relays for minute electric currents (
∗
1)
as shown below.
<Field wiring specifications>
Recommended wire: sheathed PVC cord or 2-wire cable of 0.75 - 1.25mm
2
Wiring length: Within 100m. Separate from the power line to prevent malfunctions.
z
Examples of wire connection and cautions:
Outdoor unit
Booster unit
X1A
X1M
A6P
A
B
C
ON
OFF
REMOTE
4
1
3
2
SIS
X3M
1
2
OFF: stop
ON : operation
Field wiring area
REMOTE OFF
ON
Turn the operation switch to "Remote."
(Common to outdoor units and booster units)
Operation switch (S1S)
···············
X80A
X801M
ON
OFF
DS1
A3P
1 2 3 4
ON
OFF
REMOTE
3
1
4
2
SIS
X2M
ORG
PNK CRY
PNK
1
2
In case of remote switch
Switch
Field wiring area
3 2 1 LNOP COM
1
2
Power
Power
Terminal
strip
X3M
Outdoor
unit
Contact
(
∗
1)
Contact relay for minute
electric current
(field supply)
External thermo.
(field supply)