![Daikin LCBKQ3AV1 Скачать руководство пользователя страница 211](http://html.mh-extra.com/html/daikin/lcbkq3av1/lcbkq3av1_service-manual_501887211.webp)
SiBE811001EB
Troubleshooting
CONVENI-PACK
210
8.4.31 3-sensor Error
Error Code
H0
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Error is detected from the values detected by pressure sensors and temperature sensors
(thermistors).
Error Decision
Conditions
3 or more out of the pressure sensors and the temperature sensors (thermistors) causes a
"Sensor error", respectively.
Supposed
Causes
Defective connection of sensor
Defective outdoor unit PCB
Troubleshooting
∗
1.List of relevant error codes and connectors
Relevant thermistor
LRYEQ16AY1
Electric symbol
Connector
Outdoor air thermistor
R1T
X18A
Discharge pipe thermistor (M1C)
R31T
X29A
Discharge pipe thermistor (M2C)
R32T
Discharge pipe thermistor (M3C)
R33T
Suction pipe thermistor
R21T
X30A
Suction pipe thermistor
R22T
Plate type heat exchanger outlet thermistor
R4T
Liquid temperature thermistor (outdoor unit heat exchanger outlet)
R6T
High pressure sensor
S1NPH1
X32A
Low pressure sensor (Refrigeration)
S1NPL1
X31A
Low pressure sensor (Air conditioning)
S1NPL2
X31A (Sub PCB)
Intermediate pressure sensor
S1NPH2
X32A (Sub PCB)
Properly connect it.
NO
Replace the relevant sensor.
NO
Replace the outdoor unit PCB
(control PCB).
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
∗
3 or more sensors error.
Check for the error history (error code)
on the remote controller to identify 3
or more malfunctioning sensors. (
∗
1)
Check the malfunctioning sensor
identified for their connector connection.
Is the resistance
normal? (
∗
1)
Is the resistance normal?
Troubleshoot according to the error
code of each error sensor. (See the
flowchart corresponding to each error
code.)
YES