SiBE811001EB
Troubleshooting
CONVENI-PACK
238
Refer to P.291.
Stop (standby) before
the fan rotates.
Stop (standby) when the
compressor starts up.
The
U2
error recurs.
Turn ON the power supply, and start
operation.
NO
NO
A
Replace the noise filter PCB
(A3P).
(Defective noise filter)
YES
Replace the inverter PCB (A4P).
∗
If the inverter PCB is badly
damaged, recheck the
compressor.
YES
Check the harness.
YES
Continue the operation.
∗
Causes: Instantaneous
power failure (open phase),
noises, or else.
NO
CHECK 4
Has the inverter PCB
caused damage?
Remove and insert the connectors
shown below.
X4A (A4P)
↔
X20A (A1P)
X6A (A4P)
↔
X28A (A1P)
NO
YES
Is the power transistor
normal?
Replace the inverter PCB (A4P).
NO
Replace the inverter PCB (A4P).
∗
If the inverter PCB is badly
damaged, compressor and
fan motor are likely to get
defective.
YES
CHECK 4