SiBE811001EB
Field Setting
CONVENI-PACK
126
<Operation mode: 40-59>
Tax1, Tay1, Tax2, and Tay2 can be set in setting Page 2-21.
[2-6] Setting the AIRNET address
The AIRNET address is represented as a binary number using 6 digits. Refer to the example below.
Ambient temperature
The number of
compressor (H/P side)
H1P
H2P
H3P
H4P
H5P
H6P
H7P
1
2
Fan tap
Factory
setting
Ambient temp.
≤
Tax1
8
9
k
h
h
h
h
h
k
Tay1< Ambient temp.
≤
Tax2
Ambient temp. > Tay2
Set 1
Ambient temp.
≤
Tax1
10
11
k
h
h
h
h
k
h
Tay1< Ambient temp.
≤
Tax2
9
10
Ambient temp. > Tay2
8
9
Set 2
Ambient temp.
≤
Tax1
11
11
k
h
h
h
k
h
h
Tay1< Ambient temp.
≤
Tax2
10
11
Ambient temp. > Tay2
9
10
Set 3
Ambient temp.
≤
Tax1
11
11
k
h
h
k
h
h
h
Tay1< Ambient temp.
≤
Tax2
Ambient temp. > Tay2
Fan tap
9 ~ 11 Tap
8 ~ 11 Tap
8 ~ 11 Tap
Tax1
Tay1
Tax2
Tay2
Tamb: ambient temp. ˚C
Tax1
Tay1
Tax2
Tay2
H1P
H2P
H3P
H4P
H5P
H6P
H7P
0°C
2°C
5°C
7°C
k
h
h
h
h
h
k
-5°C
-3°C
0°C
2°C
k
h
h
h
h
k
h
-10°C
-8°C
-5°C
-3°C
k
h
h
h
k
h
h
Example (1)
The address in example (1) is 010110 (binary) which represents 16 + 4 + 2 = 22 (decimal).
Consequently, the address is 22.
∗
Before setting the AIRNET address, stop the outdoor unit by setting the operation switch
(S1S) to "Stop". Otherwise, the outdoor unit may fail.
16
32
8
2
4
1