Troubleshooting
SiBE811001EB
273
CONVENI-PACK
Refer to P.291.
Cancel the melting state of
refrigerant.
Refrigerant is melting.
Recheck the compressor/
refrigerant circuit.
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Continued from the previous page.
(Start failure due to aged operation.)
YES
Replace the inverter
compressor.
Check if the insulation
resistance of the compressor
is 100k
Ω
or more.
NO
YES
Replace the compressor
inverter PCB.
Check if the power transistor
is normal.
NO
Replace the inverter
compressor.
Broken inside the
compressor
YES
NO
CHECK 4
CHECK 4