Field Setting
SiBE811001EB
121
CONVENI-PACK
Setting modes (Page 3 (service use))
These numbers represent the number of times to press the BS2 button to select each setting.
No.
Display of setting items
Display of setting conditions
Setting item
H1P H2P H3P H4P H5P H6P H7P
1
Mask setting for detecting error
for LP1 drop on refrigeration
equipment
k
h
h
h
h
h
k
2
Mask setting for detecting error
for LP2 drop on air conditioning
equipment
k
h
h
h
h
k
h
3
Decision of outdoor air
temperature degree when
cooling and heating change
k
h
h
h
h
k
k
4
Condition of LP for load-up
k
h
h
h
k
h
h
5
Correction temperature
difference setting
k
h
h
h
k
h
k
7
Back-up output setting when AIR
NET is set
(Output method of Caution output
during communication box
connection)
k
h
h
h
k
k
k
8
Pressure gauge kit error display
setting
k
h
h
k
h
h
h
12
100% heat recovery
→
partial
heat recovery transitional high
pressure setting
k
h
h
k
k
h
h
22
Pressure gauge kit lights-OFF
setting
k
h
k
h
k
k
h
41
Amount of load-up step
(Enhancing flexibility of field
setting of INV. compressor load-
up rate)
k
k
h
k
h
h
k
43
Extension of defrost end time by
high pressure.(HP > 2.256MPa)
k
k
h
k
h
k
k
45
Selection of the indoor fan while
defrost is driven
Purpose)
It uses it as an adjustment at
defrost intervals.
Factory set: OFF
Refer to details to another page.
k
k
h
k
k
h
k
46
Prohibition setting of defrost
terminated prematurely
Remark)
Defrost such as Lp2 decline,
when it is not successful, the
next time, half the defrost
interval.
If you enable this setting, you
can mask this function.
k
k
h
k
k
k
h
H1P H2P H3P H4P H5P H6P H7P
Detecting error for LP1 drop permit
(factory setting)
k
h
h
h
h
h
k
Mask setting for detecting error for LP1
drop
k
h
h
h
h
k
h
H1P H2P H3P H4P H5P H6P H7P
Detecting malfunction for LP2 drop
permit (factory setting)
k
h
h
h
h
h
k
Mask setting for detecting malfunction
for LP2 drop
k
h
h
h
h
k
h
H1P H2P H3P H4P H5P H6P H7P
30°C (factory setting)
k
h
h
h
h
h
k
28°C
k
h
h
h
h
k
h
27°C
k
h
h
h
k
h
h
25°C
k
h
h
k
h
h
h
H1P H2P H3P H4P H5P H6P H7P
LP1 > 0.0294 + Minimum Hz LP (factory setting)
k
h
h
h
h
h
k
LP1 > 0.196MPa
k
h
h
h
h
k
h
LP1 > 0.245MPa
k
h
h
h
k
h
h
LP1 > 0.294MPa
k
h
h
k
h
h
h
Ta
Minimum Hz LP
Ta > -21
0.196MPa
Ta
≤
-21
0.157MPa
H1P H2P H3P H4P H5P H6P H7P
Correction temperature difference = 0 (factory setting)
k
h
h
h
h
h
k
Correction temperature difference = 1
k
h
h
h
h
k
h
Correction temperature difference = 2
k
h
h
h
k
h
h
Correction temperature difference = -1
k
h
h
k
h
h
h
H1P H2P H3P H4P H5P H6P H7P
With output during back-up (factory setting)
k
h
h
h
h
h
k
Without output during back-up
k
h
h
h
h
k
h
H1P H2P H3P H4P H5P H6P H7P
With error display (factory setting)
k
h
h
h
h
h
k
Without error display
k
h
h
h
h
k
h
H1P H2P H3P H4P H5P H6P H7P
OFF: Hpn = 2.84MPa
k
h
h
h
h
h
k
Set 1: Hpn = 2.94MPa
k
h
h
h
h
k
h
Set 2: Hpn = 2.75MPa
k
h
h
h
k
h
h
Set 3: Hpn = 2.65MPa
k
h
h
k
h
h
h
H1P H2P H3P H4P H5P H6P H7P
7-segment display ON (factory setting)
k
h
h
h
h
h
k
7-segment display OFF
k
h
h
h
h
k
h
H1P H2P H3P H4P H5P H6P H7P
Amount of INV step-up 3 (factory setting)
k
h
h
h
h
h
k
Amount of INV step-up 2
k
h
h
h
h
k
h
Amount of INV step-up 4
k
h
h
h
k
h
h
Amount of INV step-up 1
k
h
h
k
h
h
h
H1P H2P H3P H4P H5P H6P H7P
+0min. (factory setting)
k
h
h
h
h
h
k
+2 minutes
k
h
h
h
h
k
h
+4 minutes
k
h
h
h
k
h
h
+6 minutes
k
h
h
k
h
h
h
+8 minutes
k
h
k
h
h
h
h
indoor fan
H1P H2P H3P H4P H5P H6P H7P
Set 0
(Factory set)
OFF
k
h
h
h
h
h
k
Set 1
LL
k
h
h
h
h
k
h
Set 2
L
k
h
h
h
k
h
h
Set 3
H
k
h
h
k
h
h
h
Set 4
L (Ta < 5.)
k
h
k
h
h
h
h
Set 5
H (2-15,17
Synchronization)
k
k
h
h
h
h
h
H1P H2P H3P H4P H5P H6P H7P
Don't care (factory setting)
k
h
h
h
h
h
k
Prohibition of defrost terminated prematurely
k
h
h
h
h
k
h