Troubleshooting
SiBE811001EB
275
CONVENI-PACK
8.5.17 Inverter Over-Ripple Protection
Error Code
P1
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Imbalance in supply voltage is detected in PCB.
Error Decision
Conditions
When the amplitude of the ripple exceeding approx. 6V
Ripple voltage: 35A X 240 sec.
Supposed
Causes
Open phase
Voltage imbalance between phases
Defective main circuit capacitor
Defective inverter PCB
Defective K1M relay in inverter PCB
Improper main circuit wiring
Inadequate power supply etc.
Troubleshooting
∗
1. Measure voltage at the X1M power supply terminal block.
∗
2. Measure voltage at connector (R, S and T wire pins) of the diode module inside the inverter while the compressor is running.
LED Indications
First digit
l h k l h h h
Second digit
l k h h h h l
Open phase
Normalize the field cause.
Open phase?
Imbalance in supplied
voltage is in excess of 6V.
∗
1
Fix power supply voltage
imbalance.
YES
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
NO
Part or wiring defect
After turning the power supply
OFF, check and repair the main
circuit wiring or parts.
(1) Loose or disconnected
wiring between power
supply and inverter
(2) K1M contact disposition,
fusion or contact is poor.
(3) Loose or disconnected noise
filter
Is the voltage imbalance
applied to the inverter in
excess of 6 V?
∗
2
YES
<When voltage monitoring is possible:>
measure
Explanation for users
NO
Using a device capable of constant
recording of power supply voltage
record power supply voltage
between 3 phases (R-S, S-T, R-T)
for about 1 continuous week.
Power supply voltage imbalance.
Even if the power supply voltage is
not unbalanced when measuring it,
there are many cases where it gets
unbalanced during night-time (around
6:00PM to 10:00PM).
No abnormalities are observed
in the power supply, but the
imbalance in voltage recurs.
∗
In accordance with "notification of inspection results" accompanying spare parts.
Be sure to explain to the user that there is a "power supply
imbalance" for which DAIKIN is not responsible.
Give the user a copy of "notification of inspection results" and leave
it up to him to improve the imbalance.
Replace the inverter PCB.