Field Setting
SiBE811001EB
111
CONVENI-PACK
Image of change in Hz in AC17 ver.139 and later
• Set (3 - 04) condition
• Target Lpm converted to evaporative
tempe 3˚C + set (3 - 05)
HP < 2.94 MPa MODE 8 ~ 30, 74, 75
HP < 2.74 MPa MODE 43 ~ 59, 64, 65
Target Lpm + 0.015 MPa
Low pressure
Range which can change the
amount changed in the current step
+1 step range
-1 step range
Range which slows down
with -3 steps or more
Hz maintaining range
AC17: Field setting 3-41
Range which accelerates
with the step amount set in
the setting mode
Target Lpm
Target Lpm - 0.015 MPa
Target Lpm - 0.08 MPa
(MODE
≠
17, 24)
&