SiBE811001EB
Outline of Functions (Outdoor unit)
CONVENI-PACK
94
(11) Indoor EV control (Only forced instructions from outdoor unit provided.)
OR
& OR
Indoor EV control
Instructions to shut down completely when only refrigeration is operating
Indoor SH control
Indoor freezing prevention control
Indoor overload control
Indoor SC control
Control indoor thermostat ON
Control indoor thermostat OFF
• Operation mode: 0, 29, 30, 35– – – Indoor EV = 0pls instruction
<Freezing prevention conditions>
<Freezing prevention reset conditions>
<Freezing prevention control>
• Operation mode: 5, 6, 7, 8, 11, 12, 17, 24 & in defrost operation & SH2
Control at target SH = 5˚C
• Judgement for wet during defrosting operation
Opening degree of indoor EV turned down.
• During defrost IN (Except operation mode: 74, 75, 80)
Opening degree of indoor EV set to 0pls
→ (
20 seconds or
(LP2 < f (R2T – 5˚C, 0.49MPa))
→
Indoor EV opened gradually
SH2: Suction SH for air conditioning
R2T: Indoor liquid pipe thermistor
f(R2T–5˚C): Saturation pressure calculated by
indoor liquid temperature thermistor
R3T: Indoor gas pipe thermistor
&
• Operation mode: 5, 6, 7, 8, 11, 12, 17, 24
• LP2 > 0.882MPa continues for 11 consecutive min. or more
&
• Min (Indoor EV_pls) < 1000pls
• Min (R3T–R2T) > 8˚C
• Opening degree of indoor EV added
• Target SH = 3˚C is instructed to indoor unit
(Indoor unit instructed to set absolute opening
degree, adds it, and continues sending target
SH = 3˚C after pulling up the opening degree of EV.)
is met
• Operation mode: 0, 29, 30, 35 heating mode
&
OR
• Tc – R2T
≤
5˚C continues for 2 consecutive min. or more
• Tc – R3T
≤
2˚C continues for 3 consecutive min. or more
• Tc – R3T
≤
2˚C
• Tc – R3T > 2˚C
• HP > 2.94MPa
→
Indoor EV_pls = 288pls
Opening degree of indoor EV added
Opening degree of indoor EV: 0pls instruction
•
above conditions are met
Controls LP2 at a constant value when 5˚C < target SH < 10˚C
&
OR
&
• LP2 < 0. Correction Te(Changeable by
service mode, 2-34)– – Condition A
• HP > 2.646MPa
• Operation mode: 8 to 24
• LP2 < 0. Correction Te (Changeable by service
mode, 2-34)– – Condition B
• Operation mode: Heating mode & Redundant refrigerant recovery 3
Opening degree of indoor EV: 1984pls
• Operation mode: Heating mode other than partial heat recovery & within 4 min. after indoor thermostat ON
Opening degree of indoor EV: 1984pls
• Operation mode: Heating mode of partial heat recovery & within 4 min. after indoor thermostat ON
→
"Control
indoor thermostat ON" or "Control indoor thermostat OFF"
• Operation mode: Heating mode other than partial heat recovery & 4 min. have passed after indoor thermostat ON
Without thermostat ON: Opening degree of indoor EV: 1984pls
With thermostat ON: Thermostat ON– – Opening degree of indoor EV: 1984pls or "Control indoor thermostat ON"
Thermostat OFF– – Opening degree of indoor EV: 288pls
• Operation mode: Heating mode of partial heat recovery & 4 min. have passed after indoor thermostat ON
→
"Control indoor thermostat ON" or "Control indoor thermostat OFF"
• Indoor EV_pls < 272pls
→
Indoor EV_pls = 576pls
• Indoor EV_pls > 272pls
→
Control target SC = 5˚C
288
≤
Indoor EV_pls
≤
1984pls
• HP > 2.94MPa
→
Indoor EV_pls = 1984pls
• 8 minutes have passed after startup
OR
• (LP2 < 0.588MPa & Min(R2T) < 1˚C) cumulative 20 minutes or more
• (LP2 < 0.529MPa & Min(R2T) < -1˚C) cumulative 4 minutes or more
• 50Hz
OR
• (LP2 < 0.549MPa & Min(R2T) < 1˚C) cumulative 20 minutes or more
• (LP2 < 0.49MPa & Min(R2T) < -1˚C) cumulative 4 minutes or more
• 60Hz
&
&
Condition A
Condition B
Correction Te Set 2-34
Set 0
0MPa
(Factory setting)
0.049MPa
Target Te 5˚C
Target Te 1˚C
Target Te 3˚C
Target Te 5˚C Target Te = 8˚C
Target Te = 6.5˚C
0.108MPa
Set 1
Set 2