Outline of Functions (Outdoor unit)
SiBE811001EB
87
CONVENI-PACK
(5) High pressure control
• Tf > Fm –5˚C
84˚C
Fm
• HP
≥
2.45MPa
• Operation mode
≠
5, 6, 7
• Lpm < 0.588MPa
• HP > 1.862MPa
• Lpm
≥
0.588MPa
• HP > Lpm + 1.274MPa
&
OR
&
&
OR
---
<Condition 1>
<Condition 2>
<Condition 3>
Increase fan tap with 1 tap (for every 60 seconds)
Increase fan tap with 2 taps (for every 60 seconds)
• HP
≥
2.45MPa
• TcL > Ta + 18˚C
&
---
Makes the fan tap maximum.
---
• HP
≥
2.744MPa
• HP > A MPa
• Except for the below condition
When the above condition is released.
STD compressor stops
High pressure control
Drooping at sudden
increasing of high pressure
Normal high pressure control
INV. fin cooling control
Fan control in cooling
Outdoor unit fan UP
During normal
operation
During high pressure
increasing is drooping 1
• HP > B MPa
When the above condition is released.
During normal
operation
During high pressure
increasing is drooping 2
3.283MPa
3.332MPa
3.185MPa
3.234MPa
Heating
Cooling
A: (HP_ Sudden increasing)
B: (HP_Droop 1)
Outdoor
unit fan
UP
Maintain
outdoor
unit fan
Outdoor
unit fan
DOWN
• TcL: High pressure equivalent saturation
temperature calculated by HP sensor
• Ta: Outdoor air temperature
• Fm: Drooping value of fin temperature
• Tf: INV. fin temperature
Dropping of STD compressor or
INV. Compressor
• Reduce fan tap with 2 - 3 taps
(for every 15 seconds)
• Tf < Fm –15˚C & operation mode:
64, 65, 70
• Increase fan tap with 1 tap
(for every 15 seconds)
• Tf < Fm –10˚C continues for
consecutive 3 minutes or more