System Configuration
SiBE811001EB
13
CONVENI-PACK
2.5
Regarding R-410A Selection
The freezing region is realized by an industry first R-410A as a heat-source unit.
The GWP of the R-410A liquid refrigerant becomes about half R-404A.
The refrigerant effect from the economizer and R-410A expands with respect to R-404A, R-22 refrigerant, the
circulating volume of the liquid refrigerant can be reduced with equivalent performance, the pipe size can be reduced
with respect to R-404A and R-22, since there is little pressure loss, and consequently the usage volume of the piping
and refrigerant can also be reduced.
2.6
Indoor Units to be Connected
Indoor unit models to be connected are listed in the table below.
• Indoor unit for air conditioning that can be connected
_Mark····· Indoor unit to which support is scheduled by R-410A CONVENI-PACK
(Individual driving control/For individual remote control)
¡
_Mark ····· Indoor unit for air conditioning to which support is scheduled by R-410A CONVENI-PACK
(The same driving control/ For one remote control)
<Restriction matter>
The minimum air conditioning total capacity ··· 8HP
The maximum air conditioning total capacity ···12HP
The maximum indoor unit connection number: 6 or less
Caution
The indoor unit for air conditioning does not operate until its cooling capacity exceeds 4 HP.
For this reason, do not connect remote controllers individually to the indoor unit for less than
4 HP when using heating/cooling operations. The indoor unit for air conditioning does not
operate until the capacity of the indoor unit for air conditioning of CONVENI-PACK exceeds 3
HP on heating. For this reason, do not connect the remote controller individually to the indoor
unit for less than 3 HP when operating the heating only machine.
Set up the indoor unit for the air conditioning driven simultaneously in the same space.
Item
R-410A R-404A
R-22
Ozone Depletion Potentials (ODP)
0
0
0.05
Global Warming Potentials (GWP)
1975
3920
1810
Theoretical COP Ratio (
∗
1)
91%
85%
100%
Theoretical Cooling Capacity Ratio (per unit
area) (
∗
1)
145%
93%
100%
Pressure Loss Ratio (Same performance,
same pipe size)
68%
167%
100%
Refrigerant Efficiency Ratio with or without
Economizer (
∗
2)
Yes
No
No
125%
65%
100%
(
∗
1) Evaporating temperature: -40°C, Condensing temperature: 45°C
(
∗
2) Evaporating temperature: -40°C, Condensing temperature: 45°C
R-22, R-404A: Subcooling 5°C/
Superheated 8°C
Econ R-410A: Subcooling 20°C/
Superheated 8°C
R-22
1810
R-404A
3920
R-410A is adopted
R-410A
1975
Ozone Depletion
Potentials
A zero Ozone Depletion
Potentials
Global
Warming
Potentials
Global
Warming
Potentials
Global
Warming
Potentials
Typical Model
50
63
80
100
125
200
250
Capacity Range
2.0HP
2.5HP
3.2HP
4.0HP
5.0HP
8.0HP
10.0HP
Round-flow cassette type (FXFQ)
¡
¡
¡
Double-flow cassette type (FXCQ)
¡
¡
¡
Ceiling mounted corner cassette type (FXKQ)
¡
Ceiling built-in type (FXSQ)
¡
¡
¡
Ceiling mounted duct type (FXMQ)
¡
¡
¡
Ceiling suspended type (FXHQ)
¡
Ceiling suspended cassette type (FXUQ)
Concealed floor standing type (FXNQ)
¡
¡
Floor standing type (FXLQ)
¡
¡