SiBE811001EB
Troubleshooting
CONVENI-PACK
244
8.4.55 Transmission Error between Indoor and Outdoor Units in the Same
System
Error Code
U9
Applicable
Models
All indoor models
LRYEQ16AY1
Method of Error
Detection
Detect error signal for the other indoor units within the circuit by outdoor unit PCB.
Error Decision
Conditions
When the error decision is made on any other indoor unit within the system concerned.
Supposed
Causes
Defective transmission within or outside of other system
Defective electronic expansion valve in indoor unit of other system
Defective PCB of indoor unit in other system
Improper connection of transmission wiring between indoor and outdoor unit
Troubleshooting
All the units are
indicating “
U9
”.
"
U9
" has been
displayed for 2
minutes or more.
YES
Continue operation.
NO
Re-diagnose by display after
passage of 2 minutes or more.
NO
The outdoor unit PCB indicated
by the error code “
U9
” is
normal.
Check for the indoor unit of
other system, and then conduct
troubleshooting by diagnosis
according to the Error Code
Flowchart.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Turn ON all indoor units.