SiBE811001EB
Troubleshooting
CONVENI-PACK
186
8.4.15 Room Temperature Thermistor in Remote Controller Abnormality
Error Code
CJ
Applicable
Models
All indoor models
Method of Error
Detection
Error detection is carried out by temperature detected by room temperature thermistor in remote
controller
Error Decision
Conditions
When the room temperature thermistor in remote controller becomes disconnected or shorted
while the unit is running.
∗
Error code is displayed but the system operates continuously.
Supposed
Causes
Defective remote controller thermistor
Defective remote controller PCB
Troubleshooting
Note:
∗
1. How to delete “the record of error codes”.
Press the “Operate/ Stop” button for 4 seconds and more while the error code is displayed in the
inspection mode.
Clear the malfunction code history.
(
∗
1)
Is "
CJ
" displayed on the
remote controller?
Replace the remote controller.
YES
External factor other than
equipment error.
(for example, noise etc.)
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.