Troubleshooting
SiBE811001EB
253
CONVENI-PACK
8.5.3 High Pressure Switch Abnormality
Error Code
E3
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
The protection device circuit checks continuity in the high pressure switch
Error Decision
Conditions
When the high pressure switch is actuated
Operating pressure: 2.2MPa
Reset pressure:
1.85MPa
Supposed
Causes
Insufficient service space
Suction air temperature of booster unit is 43°C or more
Defective high pressure switch
Wire broken in high pressure switch harness
Defective connection of high pressure switch connector
Obstacles at the air inlet
Defective outdoor unit fan
Refrigerant overcharged
Stop valve is not opened
Defective outdoor unit main PCB
LED Indications
First digit
l h k h h l l
Second digit
l k h h h l l