8.4.49 Reverse Phase, Open Phase
Error Code
U1
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
The phase of each phase are detected by reverse phase detection circuit and right phase or
reverse phase are judged.
Error Decision
Conditions
When a power supply is reverse phase, or T phase is open phase.
Supposed
Causes
Power supply reverse phase
T phase open phase
Defective outdoor unit PCB
Troubleshooting
Fix the open phase. Requires
inspection of field power supply
section.
There is an open phase
at the power supply (T
phase) terminal section
(X1M) of the outdoor unit.
Replace the outdoor unit PCB
(A1P).
YES
Reverse phase
Counter measure of the problem
is completed by phase
replacement.
Operation is normal if one
place of power supply line
phase is replaced.
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
NO