SiBE811001EB
Troubleshooting
CONVENI-PACK
282
Troubleshooting
Reset the power supply.
Check if outdoor unit
PCB or booster unit
PCB has been
replaced. Or check if
indoor/outdoor,
outdoor/ outdoor
relay wires has been
modified.
Check if all the indoor
remote controllers within
the same refrigerant
circuit display “
U4
”.
Check if the indoor/
outdoor, outdoor/ outdoor
relay wires are normal.
Check if the voltage
between R, S terminals
on the booster unit PCB
is 200V.
Check if the normal
condition monitor for the
micro-computer (HAP) on
the booster unit PCB
blinks.
Check if the LED in
preparation mode
(H2P) on the booster
unit PCB blink.
The fuse on the booster
unit PCB is blown.
Lights do not go
out for 10 minutes
or more.
Check if the indoor/
outdoor, outdoor/ outdoor
relay wires are normal.
Replace the booster unit main
PCB.
NO
NO
NO
Replace the indoor unit PCB.
YES
YES
Press the RESET button on the
main PCB of the outdoor unit.
Keep pressing for 5 seconds or
more.
YES
Press the RESET button on the
main PCB of the master outdoor
unit. Keep pressing for 5
seconds or more. (Operation
does not start for a maximum 10
minutes.)
NO
Correct the connecting wires.
Correct the voltage (200V).
NO
Replace the fuse.
YES
YES
Correct the relay wires.
NO
Replace the booster unit main
PCB.
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
NO
YES
YES
YES
NO
YES
NO