SiBE811001EB
Field Setting
CONVENI-PACK
130
[2-11] Evaporating temperature correction setting during low night noise operation
Set this to correct the evaporating temperature setting for low night noise operation by time. Change the [Low night
noise operation start setting] and [Low night noise operation end setting] as necessary. (The controller recognizes the
time using AIRNET.)
Detailed setting procedures
Factory setting: This feature works during time period from settings 2-8 and 2-9.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
+1°C (Factory setting)
k
h
h
h
h
h
k
+2°C
k
h
h
h
h
k
h
+3°C
k
h
h
h
k
h
h
+5°C
k
h
h
k
h
h
h
BS1
BS2
BS3
BS4
BS5
BS1
BS2
BS3
BS4
BS5
BS1
BS2
BS3
BS4
BS5
BS1
BS2
BS3
BS4
BS5
BS1
BS2
BS3
BS4
BS5
BS1
BS2
BS3
BS4
BS5
LED
(1)
SW
H1P
H2P
H3P
H4P
H5P
BS1
BS2
BS3
BS4
BS5
H6P
H7P
LED
(2)
SW
H1P
H2P
H3P
H4P
H5P
H6P
H7P
LED
(3)
SW
H1P
H2P
H3P
H4P
H5P
H6P
H7P
LED
(4)
SW
H1P
H2P
H3P
H4P
H5P
H6P
H7P
LED
LED
(5)
SW
H1P
H2P
H3P
H4P
H5P
H6P
H7P
LED
(6)
SW
H1P
H2P
H3P
H4P
H5P
H6P
H7P
LED
(7)
SW
H1P
H2P
H3P
H4P
H5P
H6P
H7P
SW
: ON
: OFF
: BLINK
: BS button
(1) Page 0
(Normal operating condition)
Press and hold BS1 (MODE) for 5 seconds.
(4) Previous setting status flashes
(Setting status shown at left: OFF)
Press BS2 (SET) to cycle through the correction values.
Press BS2 (SET) a few times.
+1˚C
+2˚C
+3˚C
+5˚C
(2) Changes to Page 2
Press BS2 (SET) 11 times.
(3) Changes to Page 2-11
Press BS3 (RETURN) once.
(6) Confirm Page 2 settings
Press BS1 (MODE) once.
(7) Settings completed
(5) Select setting for Page 2-11
Evaporating temperature correction setting for low night noise operation
(Setting shown at left: Stop time = +2˚C)
Press BS3 (RETURN) 2 times.