Troubleshooting
SiBE811001EB
241
CONVENI-PACK
8.4.52 Transmission Error between Remote Controller and Indoor Unit
Error Code
U5
Applicable
Models
All indoor models
Method of Error
Detection
Check the system using micro-computer is signal transmission between indoor unit and remote
controller is normal.
Error Decision
Conditions
Normal transmission does not continue for 2 min. or more.
Supposed
Causes
Defective transmission between indoor unit and remote controller
Connection of 2 main remote controllers (when using 2 remote controllers)
Defective indoor unit PCB
Defective remote controller PCB
Defective transmission caused by noise
Troubleshooting
SS1 of both remote
controllers is set to
"MAIN."
Operation returns to
normal when the power is
turned OFF momentarily.
NO
YES
YES
NO
Set one remote controller to
"SUB"; turn the power supply
OFF once and then restart.
YES
Change to 2-core wiring.
YES
Replace the indoor unit PCB.
NO
Caused by either a defective
remote controller PCB or a
defective indoor unit PCB.
Replace the relevant part.
NO
NO
There is possibility of error
caused by noise. Check the
surrounding area and turn ON
again.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Using 2-remote
controllers control.
All indoor unit PCB micro-
computer monitors blink.
Multi-core wiring is
used for the indoor
unit-remote controller
transmission line.