SiBE811001EB
Troubleshooting
CONVENI-PACK
226
8.4.43 Momentary Overcurrent of Inverter Compressor
Error Code
L8
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Error is detected from the current flowing in the power transistor.
Error Decision
Conditions
When inverter secondary current is below.
(1) 19.0A or more continues for 5 seconds.
(2) 16.1A or more continues for 260 seconds.
Supposed
Causes
Compressor overload
Compressor coil disconnected
Defective inverter PCB
Disconnection wire of compressor