SiBE811001EB
Field Setting
CONVENI-PACK
136
(6) Setting mode list (booster unit)
1. Setting modes (Page 2)
These numbers represent the number of times to press the BS2 button to select each setting.
2. Setting modes (Page 2 (service use))
These numbers represent the number of times to press the BS2 button to select each setting.
3. Capacity characteristics of Booster Unit after the capacity increased
Q: COOLING CAPACITY
W: POWER CONSUMPTION
No.
Display of setting items
Display of setting conditions
Setting item
H1P H2P H3P H4P H5P H6P H7P
0
Tsp1_B: Fine-tuning setting of
evaporating temperature
(binary display)
k
h
h
h
h
h
h
1
Tsp2_B: Suction pressure loss
correction setting
k
h
h
h
h
h
k
No.
Display of setting items
Display of setting conditions
Setting item
H1P H2P H3P H4P H5P H6P H7P
4
INV. Compressor max. frequency
step control
k
h
h
h
k
h
h
19
Oil recovery continuous operation
time
k
h
k
h
h
k
k
Model
Outside
temp.
Saturated suction temp.[°C]
-45°C
-40°C
-35°C
-30°C
-25°C
-20°C
Q
W
Q
W
Q
W
Q
W
Q
W
Q
W
°CDB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
LCBKQ3AV1
LCBKQ3AV1E
20°C
1.94
1.61
2.57
1.68
3.52
1.76
4.33
2.11
5.53
2.46
6.95
2.89
27°C
1.94
1.61
2.57
1.68
3.52
1.76
4.33
2.11
5.53
2.46
6.95
2.89
32°C
1.94
1.61
2.57
1.68
3.52
1.76
4.33
2.11
5.53
2.46
6.95
2.89
38°C
1.86
1.61
2.39
1.68
3.27
1.76
4.04
2.11
5.20
2.46
6.56
2.89
43°C
1.81
1.61
2.30
1.68
3.10
1.76
3.87
2.11
5.00
2.46
6.34
2.89
H1P H2P H3P H4P H5P H6P H7P
Tsp1_B
0°C (Factory setting)
k
h
h
h
h
h
h
-1°C (-0.0196MPa)
k
h
h
h
h
h
k
-2°C (-0.0192MPa)
k
h
h
h
h
k
h
-3°C (-0.0588MPa)
k
h
h
h
h
k
k
-4°C (-0.0784MPa)
k
h
h
h
k
h
h
-5°C (-0.098MPa)
k
h
h
h
k
h
k
+1°C (+0.0196MPa)
k
h
h
h
k
k
h
+2°C (+0.0392MPa)
k
h
h
h
k
k
k
+3°C (+0.0588MPa)
k
h
h
k
h
h
h
+4°C (+0.0784MPa)
k
h
h
k
h
h
k
+5°C (+0.098MPa)
k
h
h
k
h
k
h
H1P H2P H3P H4P H5P H6P H7P
Tsp2_B
OFF: Correction value =
0°C(Factory setting)
k
h
h
h
h
h
k
Set 1: Correction value = 0~1°C
k
h
h
h
h
k
h
Set 2: Correction value = 0~2°C
k
h
h
h
k
h
h
Set 3: Correction value = 0~2.5°C
k
h
h
k
h
h
h
Set 4: Correction value = 0~3°C
k
h
k
h
h
h
h
DIP • SW4
H1P H2P H3P H4P H5P H6P H7P
OFF
ON
Step = 22
(Factory setting)
Step = 16
k
h
h
h
h
h
k
Step = 24
Step = 15
k
h
h
h
h
k
h
Step = 21
Step = 14
k
h
h
h
k
h
h
Step = 20
Step = 13
k
h
h
k
h
h
h
Step = 18
Step = 12
k
h
k
h
h
h
h
Step = 17
Step = 11
k
k
h
h
h
h
h
H1P H2P H3P H4P H5P H6P H7P
Infinity (Factory setting)
k
h
h
h
h
h
k
60 minutes
k
h
h
h
h
k
h
30 minutes
k
h
h
h
k
h
h
20 minutes
k
h
h
k
h
h
h
INV. compressor max. frequency step = 24