Troubleshooting
SiBE811001EB
271
CONVENI-PACK
8.5.15 Inverter Compressor Starting Failure
Error Code
L9
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Detect the failure based on the signal waveform of the compressor.
Error Decision
Conditions
Starting the compressor does not complete.
Supposed
Causes
Stop valve is not opened
Defective compressor
Erroneous wire connections to compressor
Large differential pressure prior to compressor startup (0.5 MPa or more)
Defective inverter PCB
Slugging of refrigerant
Too frequent ON/OFF operation due to insufficient loading
LED Indications
First digit
l h k h l l l
Second digit
l k h l h h l