SiBE811001EB
Troubleshooting
CONVENI-PACK
248
Troubleshooting
Has an indoor unit
once connected been
disconnected or
changed in address?
Is power supply to
indoor units with error
code displayed
turned ON?
Are there any broken
wires or wrong wire
connections in
transmission wiring?
Is transmission with
all indoor units
malfunctioning?
Is the setting of group
No. of the malfunctioning
indoor unit made?
Are there any broken
wires or wrong wire
connections in
transmission wiring
with the main
controller?
Is the connector for
main control settings on
the main controller
disconnected?
Make setting of the group No.
properly.
NO
NO
Reset power supplies to all
centralized control equipment
simultaneously.
YES
Turn power supply to indoor unit
ON.
NO
Fix the wiring properly.
NO
Fix the wiring properly.
NO
Connect the connector properly.
NO
Replace the central PCB.
YES
Replace the indoor unit PCB.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
NO
YES
YES
YES
YES