Troubleshooting
SiBE811001EB
147
CONVENI-PACK
List of Error Codes (LCBKQ3AV1)
No.
Item
Code
(Remote
controller
display)
Detection
device
Detection conditions
Times of retry
Retry action
Processing after error is
confirmed
R2 signal
Abnormal
stop output
Output during backup
(Only when AIRNET address is 0)
Times when using
AIRNET output
Sub-classification code
Display on
remote
controller
Reset procedure
1
Earth
leakage
failure
E2
Earth leakage
breaker
Breaker reset before 10 sec. elapsed after
turning power ON.
—
—
INV. compressor stops due to
error
(
∗
When breaker power is
restored)
∗
ON when outdoor
unit is running
—
ON if AIRNET not present
1
00
EJ
• With the operation switch for the booster ON,
recycle the power to shutdown the compressor to
enable backup operation.
• After compressor with earth leak is repaired, recycle
power with operation switch in OFF position to clear
the error.
2
High
pressure
error
E3
High pressure
switch
• HPS activated at 2.5 MPa or more
—
—
INV. compressor stops due to
error
ON when outdoor
unit is running
—
ON if AIRNET not present
1
00
EJ
Recycle booster power or reset operation switch
3
Low pressure
error
E4
Low pressure
sensor
• LP < -0.015MPa
Infinite
(After first power
up (90 sec. after
startup))
• INV. compressor stops
• INV. compressor standby: 1 - 3 min.
• Retry counter clears when start up completes
• R2 signal goes OFF during retry standby
—
OFF
—
—
—
00
EJ
• Resets automatically
• Recycle booster power or reset operation switch
5
INV. compressor stops due to
error
ON when outdoor
unit is running
—
ON if AIRNET not present
(5)
1
[E4 retry code]
5
(E4 output)
4
INV.
compressor
locked
E5
INV. PCB
Waveform of current across phases
between INV. PCB and compressor was
abnormal.
4
• INV. compressor stops
• INV. compressor standby: 3 - 6 min.
• 5
th
retry: "E5" output to AIRNET
• 5
th
retry: INV. compressor error is confirmed
• Retry counter resets when INV. compressor runs 10
min. or more in total.
• R2 signal goes OFF during retry standby
INV. compressor stops due to
error
ON when outdoor
unit is running
—
ON if AIRNET not present
(5)
1
[E5 retry code]
5
(E5 output)
00
EJ
Recycle booster power or reset operation switch
5
Y1E, Y2E
error
detected
E9
Control PCB Disconnected connector
—
—
System stops
ON when outdoor
unit is running
—
ON if AIRNET not present
1
00
EJ
Check connector, then recycle booster power
—
—
6
Discharge
pipe
temperature
error
F3
Discharge
pipe
temperature
thermistor
Td
≥
125°C
—
—
INV. compressor stops due to
error
ON when outdoor
unit is running
—
ON if AIRNET not present
(15)
1
[F3 retry code]
15
(F3 output)
00
EJ
Recycle booster power or reset operation switch
14
• INV. compressor stops
• BU_Td
≤
90°C & standby: 1.5 - 6 min.
• Retry counter decrements 1 when INV. compressor
runs 10 min. or more total.
• 15
th
retry: INV. compressor stops due to error
• R2 signal goes OFF during retry standby
7
Discharge
pipe
thermistor
error
F3
or
J3
Discharge
pipe
temperature
thermistor
Td
≥
165°C
—
—
After sensor error occurs, the
substitute value is used.
ON
—
ON if AIRNET not present
1
00
EC
or
EJ
For EC: automatically resets when
165°C > BU_Td > -20°C
For EJ: recycle power or reset operation switch
J3
These conditions continued 90 sec. or
more
EC
Automatically resets when 165°C > BU_Td > -20°C
8
Heat
exchanger
inlet
thermistor
error
J8
Heat
exchanger
inlet thermistor
With the operation switch ON, these
conditions continued 50 sec.
—
—
• After sensor error occurs, the
substitute value is used.
• Y2E_pls = 0pls
ON
—
ON if AIRNET not present
1
00
EC
Automatically resets when -43.6°C < BU_TL < 55°C
9
Heat
exchanger
inlet
thermistor
error
J9
Heat
exchanger
inlet thermistor
—
—
• After sensor error occurs, the
substitute value is used.
• Y2E_pls = 0pls
ON
—
ON if AIRNET not present
1
00
EC
Automatically resets when -43.6°C < BU_Tg < 55°C
When these conditions continue 300 sec.
—
—
Automatically resets when -43.6°C < BU_Tg < 55°C
Turn the operation switch OFF, or allow to
automatically reset when -43.6°C < BU_Tg < 55°C
10
Low pressure
sensor error
JC
Low pressure
sensor
These conditions continued 5 min.
4 (Retry count
increments 1
every 5
continuous min.)
Substitute value for BU_LP = -0.05 MPa
After error is confirmed, "JC" is
sent (BU_LP is lower than the
thermistor OFF value, so
booster stops)
INV. compressor stops
ON
—
ON if AIRNET not present
1
(retry code)
5
(JC)
00
EC
Automatically resets when -0.05 MPa < BU_LP <
1.8 MPa
These conditions continued 1 min. or more
9
INV. compressor stops
INV. compressor standby : 1 min.
INV. compressor stops due to
error
ON when outdoor
unit is running
—
ON if AIRNET not present
1
(retry code)
10
(JC)
00
EJ
Recycle booster power or reset operation switch
Abnormal stop output and output during backup in the table above are output setting in outdoor units.
&
• LP < -0.015MPa
• Start up fails to complete within
90 sec.
• Thermistor ON signal occurred
OR
• BU_Td > 105˚C continued 90 sec.
or more
• BU_Td > 110˚C continued 15 sec.
or more
• BU_Td > 120˚C
&
• INV. compressor is running
• BU_Td
≤
-20˚C
• Operation switch is ON
&
OR
&
• Operation switch is ON
• BU_TL
≤
-43.6˚C
• BU_TL
≥
55˚C
• Operating mode = 1
• Received thermostat ON
signal from outdoor unit
• Y2E pls
≥
100
&
• Tg
≤
-43.6˚C continues 50 sec.
• Operation switch is ON
&
OR
&
• Operating mode = 1
• Y2E pls > 200
• Tg
≥
35˚C
• TgSH > 35˚C
• BU_Tg > 30˚C
• Received humidity
prevention signal from
outdoor unit
&
• LP
≤
-0.05 MPa
• Operation switch is ON
&
• BU_LP
≥
18
• DC compressor is running