Outline of Functions (Outdoor unit)
CONVENI-PACK
88
• HP – LP1 < 0.294MPa (Operation for refrigeration)
• HP – LP2 < 0.294MPa (Operation for air conditioning)
• HP < Lpm + 0.686MPa
• HP > 1.274MPa
• TcL < Ta + 5˚C
• HP > 2.45MPa
• Fan tap
≥
6
OR
&
&
&
OR
OR
---
• Min(Tset – Tr) > 3~5˚C
• Max(Tset – Tr) > 7~9˚C
OR
&
Outdoor unit fan DOWN
High pressure control in heating
While the outdoor unit heat exchanger is operating in evaporating mode
(Operation mode: 40, 41, 42, 43, 46, 47, 52, 59)
100% Heat recovery operation (Operation mode: 64, 65, 70)
Partial Heat Recovery operation (Operation mode: 74, 75, 80)
• Operation mode
≠
5, 6, 7
• LP1: Low pressure for refrigeration
• LP2: Low pressure for air conditioning
• TcL: High pressure equivalent saturation
temperature calculated by HP sensor
• Ta: Outdoor air temperature
• Tset: Temperature set with remote controller
• Tr: Indoor suction air temperature
• Ta: Outdoor air temperature
HP < 2.548MPa
• When the fan-tap is not at maximum --- Increase fan tap with 1 or more (for every 5 seconds)
• When the fan-tap is at the maximum and (• Min(Tset – Tr) > 2~5˚C or Max (Tset – Tr) > 6~9˚C)
--- Shifts the mode to increase the heating capacity (Guard timer of heating capacity increasing: 3 - 30
minutes) (However, with Ta > A˚C there are cases where the heating capacity is not increased)
2.548MPa
≤
HP < 2.744MPa
• LP2 < 0.519MPa --- Increase fan tap with 1 tap (for every 5 seconds)
2.744MPa
≤
HP < 2.94MPa
• LP2 > 0.294MPa --- Reduce fan tap with 1 tap (for every 5 seconds)
HP
≥
2.94MPa or (HP
≥
2.744MPa continues for consecutive 5 minutes or more)
STD compressor stops operation
HP < 2.548MPa
• When Min(Tset – Tr) > 2~5˚C or (Max (Tset – Tr) > 6~9˚C & Ta < B˚C)
B: 20˚C (Mode 64), 25˚C (Mode 65, 70)
Shift the mode to increase heating capacity (Guard timer of heating capacity increasing: 3 - 30 minutes)
2.548MPa
≤
HP < HPn (Setting of HPn: by set 3-12) MPa
• Maintain the status
HPn MPa
≤
HP < Min. (3.087MPa, HPn + 0.245MPa) MPa
• Forcible H instruction of indoor unit fan tap [Instruction of thermostat ON/OFF (except for remote control
being stopped) to indoor unit]
(H-Instruction Releasing Condition: HP
≤
2.744MPa or when operation mode is changed)
• When indoor unit fan tap, H, has continued for 5 minutes and HP
≥
2.842
→
Shifts the four way valve-B
to be ON (Partial Heat Recovery operation mode)
HP
≥
Min. (3.087MPa, HPn + 0.245MPa) MPa
• Turns the four way valve B to be ON (Shift partial Heat Recovery operation mode)
HP
≥
3.038MPa continues for consecutive 5 seconds or more)
• Operation mode 74 & INV. compressor STEP
≤
1
→
STD1 compressor stops
• (Operation mode 74 & INV. compressor STEP > 1) or operation mode 75
→
INV. compressor 1~3
DROPPING DOWN
HP
≥
3.038MPa
• Makes the fan tap to be maximum
2.842MPa
≤
HP < 3.038MPa
• Increase fan tap with more than 1 (for every 60 seconds)
HP – f(Target Tc) > 0 & HP > Lpm + 1.274MPa
→
Increases fan-tap with 1 (for every 60 seconds)
f(Target Tc) – HP > 0 & HP < Lpm + 0.686MPa
→
Decreases fan-tap with 1 (for every 20 seconds)
• HP < f (Target Tc) – 0.294MPa
• Ta < 25˚C
• Min(Tr) < 25˚C
When condition is the same as above
→
Shift the four way valve-B to be OFF
(100 % Heat Recovery operation mode)
A: 20˚C (Except mode 41, 42), 25˚C (Mode 41, 42)
Reduce fan tap with 1 tap
(for every 20 seconds)